Pressure to Current Transducer
Displays |
Temp. Sensors | Humidity Transmitters | Pressures Transmitters |
Current Sensors
Interface Devices | Accessories
ACI/PTP
![]() |
Product Description: The ACI/PTP will accept either a 3 to 15 or 3 to 30 psig pneumatic input and converts it to a proportional 4 to 20 mA output. By adding supplied external resistors the ACI/PTP will output a proportional 1 to 5, 2 to 10, or 3 to 15 VDC signal. It is a positive current output device that is fully temperature compensated. A 1/8"-27 FNPT gauge port is included for local mechanical indication. The ACI/PTP is available in a snap track mount configuration. Some common applications include Building Automation, Process Control, Pneumatic System Monitoring, and Pneumatic to Proportional Analog Output. |
Product Specifications:
| Supply Voltage |
Regulated 24 VDC +/- 10% Regulated 22 to 28 VAC | Operating Temp | 32 to 120°F |
| Supply Pressure |
15 psig max
(PTP 3 to 15) 30 psig max (PTP 3 to 30) | Supply Current | 50mA max @ 24VDC |
| Accuracy | 1% of full scale | Input Ranges | 3 to 15 or 3 to 30 psig |
| Analog Outputs | 1-5, 2-10, 3-15VDC or 4-20mA | Load Impedance | 750 Ohms max (current output) |
| ACI/PTP | -[] | -[] |
| (1) 3 TO 15 psig | () No Gauge | |
| (2) 3 to 30 psig | (G) with Gauge |
Back To Top