Smoke Detectors


ACI/RW-024 Series
 

Product Description:

The ACI/RW024 Series duct smoke detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct. These devices are designed for the prevention of smoke recirculation in areas by the air handling systems. Fans, blowers, and complete systems may be shut down in the event of smoke detection. The 24 volt models will operate on either 24 VAC or VDC.

The ACI/RW024 may utilize either a photoelectric or ionization detector head. Each of the devices contains (2) form "C" Alarm Contacts and (1) form "C" Trouble Contact.

Visual indicators, pilot and alarm, are mounted on the housing front for status indication. A manual test/reset switch is also provided on the front of the detector.

Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7.5") is provided with the detector housing. Intake sampling tubes, which must be ordered separately, are supplied in three standard lengths.

Product Specifications:
Supply Voltage 24 VAC/VDCSupply Current 24 VAC: 61mA standby, 160mA Alarm (max)
24VDC: 25mA standby, 70mA Alarm (max)
Relay Outputs Alarm:(2) form "C" relays 10A@115 VAC
Trouble:(1) form "C" relay 5A @115 VAC
Case 18 Gauge steel back box, clear plastic cover
Operating Temp 30 to 120°F(0to 49°C) Weight 4 lbs.
Operating Humidity 10% to 80% RH Dimensions 10" H x 8.25" W x 2.25" D
Air Velocity 300 to 4,000 ft./minute Approval Underwriters Laboratories Listed, (UL268A)






Ordering Information:
Smoke Detectors
ACI/RW-024- [ ]
(N) - Ionization Detection Head
(P) - Photelectric Detection Head
Sampling Tubes
ACI/STS- [ ]
(2.5) - Sampling tube for 6" to 2.5' Duct Widths
(5.0) - Sampling tube for 2.5' to 5' Duct Widths
(10.0) - Sampling tube for 5' to 10' Duct Widths

Example: ACI/RW-024-N or ACI/STS-2.5