Specifications
  • ANSI/IEEE C62.41-2002
  • IEC 61643-1-1998
  • NEMA LS-1-1992

Branch Panel Protection

Model 120LS

Model
120LS

Service

Higher
Headroom
MOVs
VAC

UL SVR
500A
8x20
µs

6kV (1.2x50µs)
3kA (8x20
µs)

20kV (1.2x50µs)
10kA (8x20
µs)

-120S 120VAC, 1Ø, 2W+Gnd 180 500 550 660
-120T 120/240VAC, 1Ø, 3W+Gnd 180 500 550 660
-120Y 120/208, 3Ø, 4W+Gnd, Wye 180 500 550 660
-220Y 220/380, 3Ø, 4W+Gnd, Wye 390 1000 1110 1270
-240Y 240/415, 3Ø, 4W+Gnd, Wye 390 1000 1110 1270
-277Y 277/480, 3Ø, 4W+Gnd, Wye 390 1000 1110 1270
-347Y 347/600, 3Ø, 4W+Gnd, Wye 460 1200 1350 1580
-240DCT* 240/120/120, 3Ø, 4W+Gnd 390/180 1000/500 1110/550 1270/660
-240D 240, 3Ø, 3W+Gnd, Delta 390 1000 1110 1270
-480D 480, 3Ø, 3W+Gnd, Delta 620 1500 1640 1890
-600D 600, 3Ø, 3W+Gnd, Delta 750 1800 1830 2410

*High-leg Delta Center Tapped

Energy Absorption (8/20µs) in joules: 8,832 - 32,400J
MCG Surge Protection employs high headroom movs in our products to prevent damage to the surge protector from voltage swells on the AC power line. These swells are harmless to equipment but not to a surge protector without enough headroom designed into it. Using high headroom varistors allows the surge protector to "ride out' the swells without damaging the varistors. However, we understand that some applications require lower voltage varistors than what we provide with our standard products.

If your application requires the use of lower voltage varistors, please contact Sentinel Power, Inc at 1-800-784-7989 (US only) or 724-925-8181 and we will discuss your requirements with the factory.