Home |
Company
Info | Products |
Articles
| Contact Us | Search Our Site
| Site Map |
|
| 160MXT | MCG SURGE PROTECTION |
|
STANDARD CLASS BUILDING ENTRY PROTECTOR
|
20-Year
Warranty
UL 1449 ANSI/IEEE C62.41-1996 |
|
| DESCRIPTION | FEATURES |
| The 160MXT Series are brute
force protectors designed for installation at the entrance of large to
mid-sized facilities. The unit offers first-rate protection for 160kA
applications at the main service panel. Redundant protection and complete
diagnostics ensure continuous, reliable operation. All models include a ten
year warranty on unit; lifetime on modules.
|
|
CONFIGURATIONS: |
20kV, 1.2/50µs; 10kA, 8/20µs |
|||||||
| MODEL | SERVICE |
Higher
Headroom |
UL 1449 |
SPD |
|
|||
| Let-Thru V | Let-Thru V | |||||||
VAC |
Clamp V |
Clamp V | 1.0 ft. | 2.0 ft. | ||||
| 160MXT-120T | 120/240VAC, 1Ø, 3W+GND |
180 |
500 | 550 | 735 | 880 | ||
| 160MXT-120Y | 120/208VAC, 3Ø, 4W+GND, WYE | 180 | 500 | 550 | 735 | 880 | ||
| 160MXT-220Y | 220/380VAC, 3Ø, 4W+GND, WYE | 390 | 900 | 1040 | 1400 | 1570 | ||
| 160MXT-240Y | 240/415VAC, 3Ø, 4W+GND, WYE | 390 | 900 | 1040 | 1400 | 1570 | ||
| 160MXT-240D | 240VAC, 3Ø, 3W+GND, DELTA | 390 | 900 | 1040 | 1400 | 1570 | ||
| 160MXT-240DCT* | 240/120/120VAC,3Ø, 4W+GND | 390/180 | 900/500 | 1040/550 | 1400/735 | 1570/880 | ||
| 160MXT-277Y | 277/480VAC, 3Ø, 4W+GND, WYE | 390 | 1000 | 1040 | 1400 | 1570 | ||
| 160MXT-347Y | 347/600VAC, 3Ø, 4W+GND, WYE | 460 | 1000 | 1052 | 1440 | 1600 | ||
| 160MXT-480D | 480VAC, 3Ø, 3W+GND, DELTA | 620 | 1500 | 2000 | 2030 | 2050 | ||
| 160MXT-600D | 600VAC, 3Ø, 3W+GND, DELTA | 750 | 1800 | 2030 | 2210 | 2300 | ||
|
*High-leg Delta Center Tapped |
||||||||
|
‡UL 1449, 500A Test: A UL test setup (6" of cabling and low 500A, 8/20µs current waveform) to allow clamping voltage comparisons between SPD's made by different manufacturers. Since a protector in the field will experience a greater surge of transient energy, the low peak current of 500A does not properly reflect an SPD's true clamping and hence is of limited value. |
||||||||
SPECIFICATIONS |
||||||||
| Surge Current/Phase (8/20µs): | 1 Event - 160kA | |||||||
| Surge Life/Phase (8/20µs): | 10,000 Events: 6kA | |||||||
| Status Indicators: |
LED Status Indicators, Event Counter, Audible Alarm with Mute Switch, Protected Remote Alarm Dry Contacts |
|||||||
| Modes of Protection: | L-N, L-G, L-L, N-G | |||||||
| Operating Altitude: | 13,000ft. (4000m) | |||||||
| Temp. (Operating/Storage): | -40° to +70° C/-40° to +85° C | |||||||
| Enclosure: | NEMA 4, 14 gauge steel | |||||||
| Dimensions for 160MXT: | 12" x 15" x 5.5" (305 x 381 x 140mm) | |||||||
| Mounting for 160MXT: |
8" x 15.75"/.31"ID - 4 holes (203 x 400mm/8mm ID) |
|||||||
| Micro-Z Cable Connection: | #10 AWG | |||||||
| Micro-Z Cable Length: | 8ft. (2.44M) | |||||||
| Weight: | 35 lbs. (16.0kg) | |||||||
FILTER ATTENUATION |
||||||||
| MIL STD 220A (50ohm): | 120VAC | 240VAC | 277VAC | 480VAC | ||||
| -30db: | 100kHz | 25kHz | 80kHz | 80kHz | ||||
| -40db: | 200kHz | 100kHz | 180kHz | 180kHz | ||||
| -50db: | 280kHz | 180kHz | 210kHz | 250kHz | ||||
| -60db: | 310kHz | 200kHz | 390kHz | 390kHz | ||||
Back To Top
© 2004
Sentinel Power Inc. All rights reserved.
Last Updated 09/30/08