Specifications
  • ANSI/IEEE C62.41-2002
  • IEC 61643-1-1998
  • UL 1449, 2nd Edition
  • NEMA LS-1-1992

Main Panel Protection

Model 200LS
Model
200LS

Service

Higher
Headroom
MOVs
VAC

UL SVR
500A
8x20
µs

6kV (1.2x50µs)
3kA (8x20
µs)

20kV (1.2x50µs)
10kA (8x20
µs)

-120S 120VAC, 1Ø, 2W+Gnd 180 500 534 644
-120T 120/240VAC, 1Ø, 3W+Gnd 180 500 534 644
-120Y 120/208, 3Ø, 4W+Gnd, Wye 180 500 534 644
-220Y 220/380, 3Ø, 4W+Gnd, Wye 390 1000 1050 1212
-240Y 240/415, 3Ø, 4W+Gnd, Wye 390 1000 1050 1212
-277Y 277/480, 3Ø, 4W+Gnd, Wye 390 1000 1050 1212
-347Y 347/600, 3Ø, 4W+Gnd, Wye 460 1200 1350 1510
-240DCT* 240/120/120, 3Ø, 4W+Gnd 390/180 1000/500 1505/534 1212/644
-240D 240, 3Ø, 3W+Gnd, Delta 390 1000 1050 1212
-480D 480, 3Ø, 3W+Gnd, Delta 620 1500 1598 1802
-600D 600, 3Ø, 3W+Gnd, Delta 750 1800 1804 2018

*High-leg Delta Center Tapped

Energy Absorption (8/20µs) in joules: 13,248 - 54,000J
MCG Surge Protection employs high headroom movs in our products to prevent damage to the surge protector from voltage swells on the AC power line. These swells are harmless to equipment but not to a surge protector without enough headroom designed into it. Using high headroom varistors allows the surge protector to "ride out' the swells without damaging the varistors. However, we understand that some applications require lower voltage varistors than what we provide with our standard products.