  • ANSI/IEEE C62.41-2002
  • IEC 61643-1-1998
  • UL 1449, 2nd Edition
  • NEMA LS-1-1992

Service Entrance Protection

Model 300LS
Model
300LS

Service

Higher
Headroom
MOVs
VAC

UL SVR
500A
8x20
µs

6kV (1.2x50µs)
3kA (8x20
µs)

20kV (1.2x50µs)
10kA (8x20
µs)

-120S 120VAC, 1Ø, 2W+Gnd 180 500 520 614
-120T 120/240VAC, 1Ø, 3W+Gnd 180 500 520 614
-120Y 120/208, 3Ø, 4W+Gnd, Wye 180 500 520 614
-220Y 220/380, 3Ø, 4W+Gnd, Wye 390 1000 1008 1164
-240Y 240/415, 3Ø, 4W+Gnd, Wye 390 1000 1008 1164
-277Y 277/480, 3Ø, 4W+Gnd, Wye 390 1000 1008 1164
-347Y 347/600, 3Ø, 4W+Gnd, Wye 460 1200 1280 1450
-240DCT* 240/120/120, 3Ø, 4W+Gnd 390/180 1000/500 1008/520 1164/614
-240D 240, 3Ø, 3W+Gnd, Delta 390 1000 1008 1164
-480D 480, 3Ø, 3W+Gnd, Delta 620 1500 1566 1766
-600D 600, 3Ø, 3W+Gnd, Delta 750 1800 1776 1970

*High-leg Delta Center Tapped

Energy Absorption (8/20µs) in joules: 17,664 - 75,600J
MCG Surge Protection employs high headroom movs in our products to prevent damage to the surge protector from voltage swells on the AC power line. These swells are harmless to equipment but not to a surge protector without enough headroom designed into it. Using high headroom varistors allows the surge protector to "ride out' the swells without damaging the varistors. However, we understand that some applications require lower voltage varistors than what we provide with our standard products.