BACK
 
Specifications
  • ANSI/IEEE C62.41-2002
  • IEC 61643-1-1998
  • UL 1449, 2nd Edition
  • NEMA LS-1-1992

Service Panel Protection

Model 560LS
Model
560LS

Service

Higher
Headroom
MOVs
VAC

UL SVR
500A
8x20
µs

6kV (1.2x50µs)
3kA (8x20
µs)

20kV (1.2x50µs)
10kA (8x20
µs)

-120S 120VAC, 1Ø, 2W+Gnd 180 500 494 590
-120T 120/240VAC, 1Ø, 3W+Gnd 180 500 494 590
-120Y 120/208, 3Ø, 4W+Gnd, Wye 180 500 494 590
-220Y 220/380, 3Ø, 4W+Gnd, Wye 390 1000 976 1098
-240Y 240/415, 3Ø, 4W+Gnd, Wye 390 1000 976 1098
-277Y 277/480, 3Ø, 4W+Gnd, Wye 390 1000 976 1098
-347Y 347/600, 3Ø, 4W+Gnd, Wye 460 1200 1240 1368
-240DCT* 240/120/120, 3Ø, 4W+Gnd 390/180 1000/500 976/494 1098/590
-240D 240, 3Ø, 3W+Gnd, Delta 390 1000 976 1098
-480D 480, 3Ø, 3W+Gnd, Delta 620 1500 1532 1678
-600D 600, 3Ø, 3W+Gnd, Delta 750 1800 1736 1910

*High-leg Delta Center Tapped

Energy Absorption (8/20µs) in joules: 35,328 - 151,200J
MCG Surge Protection employs high headroom movs in our products to prevent damage to the surge protector from voltage swells on the AC power line. These swells are harmless to equipment but not to a surge protector without enough headroom designed into it. Using high headroom varistors allows the surge protector to "ride out' the swells without damaging the varistors. However, we understand that some applications require lower voltage varistors than what we provide with our standard products.

If your application requires the use of lower voltage varistors, please contact Sentinel Power, Inc at 1-800-784-7989 (US only) or 724-925-8181 and we will discuss your requirements with the factory.

Back To Top
© 2004 Sentinel Power Inc. All rights reserved.
Last Updated 09/16/05