SENSAPHONE 1400
Technical Specifications
| Environmental Inputs |
| Number of Zones: 4 |
| Zone Connector: terminal block |
| Zone Types: N.O./N.C. contact, 2.8K
(-109°
to 115°F;
-85°
to 57°C),
and 10K thermistor (-87° to 168°F; -66° to 76°C), and 4-20mA (-10,000 to 10,000) |
| Zone characteristics: 28KΩ to 2.5V (temperature/contact) or 250 Ohms to ground (4-20mA) |
| A/D Converter Resolution: 10 bits ±2 LSB |
| Zone Protection: Metal oxide varistors, and fast-acting diode clamps |
| Microphone |
| Internal: for recording custom voice messages |
| External (optional): For listening in
to on-site sounds and high sound level alarms •Mic Connector: terminal block •Mic Type: Electret Condenser •Mic Impedance: 2.2KΩ |
| Phone Interface |
| Terminals for connection to a two-wire analog telephone line |
| Line seizure terminals for connecting extension telephone devices |
| LED Indicators: (4) Zone Alarms, Sound, Power, Battery OK, Phone in Use, Output On, and System On |
| Relay Output: 2A 120VAC/2A 24VDC - Programmable for automatic or manual switching |
| Power Supply: 120VAC/9VDC 60Hz 6W wall
plug-in transformer (230VAC/9VDC 50/60Hz power supply optional) |
| Power Consumption: 5 Watts |
| Power Protection: Metal Oxide Varistor |
| Battery Backup: 6V 1.3 AH sealed gel cell, provides up to 24 hours of back up time |
| Environmental |
| Operating Temperature: 32-122°F (0-50°C) |
| Operating Humidity: 0-90% RH non-condensing |
| Storage Temperature: 32-140°F |
| Physical |
| Dimensions: 12.1"h x 7.3"w x 4.5"d |
| Weight: 5 lbs. |
| Enclosures: •Solid door Enclosure: ABS Plastic, UL94-0 Flammability rating, NEMA Type 1,2,3,3R,4,4X,12 & 13, IEC529, IP66. •Clear Door Enclosure: ABS/PC blended plastic, UL94-5VB flammability rating; [Clear Door] Polycarbonate plastic, UL94V-0 flammability rating. UV stabilized NEMA Type 1,2,3,3R,4,4X,12 &13, IEC529, IP66. |
*Specifications subject to change