Home
| Company Info | Products
| Articles | Contact
Us | Search Our Site | Site
Map
Veris | Hawkeye
| Alta Labs | Enspector | Product
List | Applications
 |
| For
monitoring both instantaneous power (kW) for demand control and
consumption over time (kWH), the VERIS 6000 series
provides high accuracy (better than 1%) with low-cost installation
to provide an excellent solution for the building owner with the
need to submeter one or more tenants or the physical plant. The
6001 meter provides a NEMA1 rated enclosure with conduit knockouts
for easy installation in almost any field environment covering
any voltage from 120V to 600V AC. The split core CT's mean that
there is no need to remove any of the primary conductors to monitor
current flow and a selectable pulse rate allows easy field setup
for any automation panel. The 6000 series also provides a contact
output for phase loss or undervoltage (adjustable by the owner)
if either condition is detected by the panel. |
Installation instructions:
- Set input voltage switch to proper voltage
- Make voltage connections using 14-26 AWG wire, fused according
to NEC requirements, being sure to observe phasing (A,B, and C)
- Install Veris "safe" CT's on primary conductors...
critical concerns for CT installation are:
- Insure that arrows on CT's point in the direction of the load
(e.g., motor or building load) and not at the source
- Insure that the CT's are matched properly to the voltage inputs
(i.e., phase A voltage matched with phase A current)
- Connect outputs from power meter to automation system
- Turn on the load being monitored
- Select the maximum pulse rate using the chart provided with
the unit
- Determine the maximum kW value for the 3 phase analog output
using the formula:
- kW maximun = (Exl cr x 1.73)/1000
- Calculate the kW value for programming the automation panel:
- kW maximun = [(Exl cr x 1.73) x (mA
out - 4)]/1000 x 16
- For additional information on power and sample formulas,
see Appendix A
Troubleshooting tips:
- If the output of the pulse or analog does not appear to match
the expected values, check that the phase loss/reversal light
is lit. If the light is unlit, the installation is probably incorrect.
Check the following:
- Make sure that the CT's are properly oriented so that the
arrows on the label are pointing towards the load and away from
the source
- Make sure that the CT's are properly matched with the voltages
(i.e., Volts A to Current A; Volts B to Current B; Volts C to
Current C)
- Make sure that the voltage selection switch is set in the
proper position for the actual input voltage
- If the installation appears to be correct, use the following
procedure to verify that all devices are wired correctly and working
properly:
- Disconnect all CT's except the phase A CT;
- Install jumper wires in the Phase B and C current inputs
- Set the pulse output switch to "Test" mode
- Verify that there is current flowing in phase A
- The "kWH" output should be flashing at a rate of
approximately 1 pulse per second (actual rate may vary depending
on the load)
- If there is not pulse at the output, reverse the white and
black CT wires on phase A. If the pulse starts, the CT is reversed.
If there is still no pulse, contact the factory
- Repeat the test for phases B and C, making sure to jumper
the unused CT inputs during each test
- If this does not correct the problem, contact the factory
for technical support
6000 series wiring diagram:
Applications are suggestions. Field applications vary; since manufacturer
does not install the devices, it is up to the installer to ensure suitability
and compliance to appropriate codes.
Back To Top
© 2004 Sentinel Power Inc. All rights reserved.
Last Updated 03/21/07